Canadian owned and operated · Shipping across North America · Low-GWP R-32

Compact-Aire
3K · 1.4K · HP

A reliable, energy-efficient and architecturally discreet through-wall heat pump for multi-residential, hospitality and retrofit projects, including hot water or electric baseboard replacement. Year-round heating and cooling with no exterior equipment and no refrigerant line sets.

7,080–11,800BTU/h rated cooling
115V or 208/230Vplug-in or hard-wired
R-32low-GWP refrigerant (GWP 675)
ETL Listed mark (Intertek) R32 refrigerant
Compact-Aire through-wall heat pump wall-mounted below a window in a bedroom
COMPACT-AIRE SERIESHeating and cooling, without giving up space, style or comfort.Slim and wall-hung, with no outdoor unit and only two wall caps outside.
CHOOSE YOUR MODEL

Three models, one cabinet design.

208/230V · 3 KW HEAT

Compact-Aire 3K

For larger rooms and suites. A 3 kW electric heater can take over from the compressor for electric-only heating when switched on.

Cooling
11,800 BTU/h
Heating at 47°F
10,900 BTU/h
Electric heat
3 kW, instead of compressor
MCA / MOP
20 A / 20 A
Size (W × H × D)
39.4″ × 22.8″ × 8.6″
3K spec sheet (PDF) →
208/230V · 1.4 KW HEATNEW

Compact-Aire 1.4K

The 3K's capacity with a 1.4 kW electric heater, for a lower electrical load where a 3 kW heater isn't needed.

Cooling
11,800 BTU/h
Heating at 47°F
10,900 BTU/h
Electric heat
1.4 kW, instead of compressor
MCA / MOP
11 A / 15 A
Size (W × H × D)
39.4″ × 22.8″ × 8.6″
1.4K spec sheet (PDF) →
115V · PLUG-INCOMING SOON

Compact-Aire HP

For single rooms. Plugs into a 115V circuit, with a 600 W electric heater that works together with the compressor in colder weather.

Cooling
7,080 BTU/h
Heating at 47°F
7,120 BTU/h
Electric heat
600 W, with compressor
Sound
30–39 dBA
Size (W × H × D)
36.81″ × 21.38″ × 7.8″
HP spec sheet (PDF) →
HOW IT WORKS

Outdoor air in and out through the wall. Comfort stays inside.

Two openings through the exterior wall let the sealed refrigeration circuit exchange heat with outdoor air. The inverter compressor adjusts its speed continuously to match the room's heating or cooling demand.

Cutaway illustration of the unit in heating mode, warm air leaving the front outlet
Heating Heat is drawn from outdoor air and delivered to the room through the front outlet.
Illustration of cool air leaving the wall-mounted unit
Cooling The same circuit runs in reverse to cool and dehumidify the room.
Illustration of the two round exterior wall vents with air flowing in and out
Outside Only two discreet wall vents. No condenser, balcony unit or line set.
VIDEO · 1:40

Meet Compact-Aire.

The Compact-Aire mascot speaks as the product: how it works, why to choose it, what it delivers and what it saves.

ENERGY EFFICIENCY

More heat out than electricity in.

The heat pump moves heat rather than making it. At rated conditions each unit delivers about 2.5 to 3.4 times more heating or cooling than the electricity it draws. The inverter compressor then slows down as the room approaches its setpoint.

COMPACT-AIRE 3K & 1.4K

Cooling95°F / 35°C outdoor
Electricity in1.21 kW
Cooling delivered3.46 kW
2.9×kW out per kW in
Heating47°F / 8°C outdoor
Electricity in0.95 kW
Heat delivered3.19 kW
3.4×kW out per kW in

COMPACT-AIRE HP

Cooling95°F / 35°C outdoor
Electricity in0.85 kW
Cooling delivered2.07 kW
2.5×kW out per kW in
Heating47°F / 8°C outdoor
Electricity in0.70 kW
Heat delivered2.09 kW
3.0×kW out per kW in

Rated capacity and power input from the 2026 WAYSOS spec sheets, heat pump only (electric back-up heat off). kW out per kW in is capacity divided by power input at the conditions shown; the heating figure is the coefficient of performance (COP). Running cost depends on climate, setpoint and electricity rate.

CONTROLS & ELECTRIC HEAT

Set it once, or let it decide.

Every mode is available from the on-board touch controls, the hand remote or the Smart Life app, with an optional third-party 24V wall thermostat.

Electric back-up heat

HP: the 600 W heater is switched on manually and runs together with the compressor to add heat in colder weather.

3K and 1.4K: the unit heats with the heat pump by default. When the 3 kW or 1.4 kW heater is activated, by holding the Electric Heater button or through a 24V thermostat on the AUX terminal, the compressor switches off and the unit runs on electric heat only. The two never run at the same time.

Cooling and heating

Setpoint adjustable from 64°F to 86°F, with Low, Medium, High and Auto fan speeds.

Auto mode

Chooses heating, cooling or fan automatically from room temperature: heating below 68°F, fan between 68°F and 77°F, cooling above 77°F.

Dehumidification and fan

Dry mode runs a fixed low fan speed for effective moisture removal. Fan mode circulates air without heating or cooling.

Timers and sleep mode

On and off timers programmable in 10-minute and 1-hour steps, set independently. Sleep mode adjusts temperature gradually overnight, lowers fan speed and dims the display.

SPECIFICATIONS

3K, 1.4K and HP compared

Through-wall heat pump specifications
MODEL COMPACT-AIRE3K COMPACT-AIRE1.4K COMPACT-AIREHPCOMING SOON
COOLING
Rated capacity (95°F)11,800 BTU/h11,800 BTU/h7,080 BTU/h
EER210.110.110.5
SEER215.5515.5513.9
Power input1,209 W1,209 W846 W
Outdoor operating range64°F to 109°F64°F to 109°F—
HEATING — HEAT PUMP ONLY
At 47°F / 8°C10,900 BTU/h · COP 3.410,900 BTU/h · COP 3.47,120 BTU/h · COP 3.0
At 17°F / −8°C7,180 BTU/h · COP 2.37,180 BTU/h · COP 2.34,405 BTU/h · COP 1.8
At 5°F / −15°C4,370 BTU/h · COP 1.644,370 BTU/h · COP 1.642,825 BTU/h · COP 1.2
HSPF28.28.27.4
Power input (47°F)947 W947 W703.4 W
Outdoor operating range——5°F to 75°F
Electric back-up heat3 kW1.4 kW600 W
Electric heat runsInstead of the compressorInstead of the compressorAlongside the compressor
ELECTRICAL & OPERATION
Power supply (V-Ph-Hz)208/230-1-60208/230-1-60115-1-60
MCA / MOP20 A / 20 A11 A / 15 A13.4 A / 15 A
Indoor airflow215–330 CFM215–330 CFM165–235 CFM
Indoor sound32 dBA32 dBA32 dBA
Safety listingETLETLETL
CERTIFICATION & REBATE DATA
AHRI certifiedIn progressIn progressIn progress
Heating at 5°F / −15°C (COP)COP 1.64COP 1.64COP 1.2
INSTALLATION
Unit size (W × H × D)39.4″ × 22.8″ × 8.6″39.4″ × 22.8″ × 8.6″36.81″ × 21.38″ × 7.8″
Wall openings (supply & exhaust)2 × 8″ dia.2 × 8″ dia.2 × 8″ dia.
Condensate drain——1.2″ dia.
Weight117 lb117 lb86 lb
DocumentsSpec sheet (PDF)Spec sheet (PDF)Spec sheet (PDF)

Heating values are for the heat pump alone at the outdoor temperatures shown. Values from current WAYSOS spec sheets (2026). Specifications may change without notice. Confirm against the current submittal before design. Compare with the Pro series →

INSTALLATION

Installed from inside the room, in a day.

Two wall openings, a bracket and a power connection. Shown here: a window-wall retrofit in an occupied suite, with the openings through an infill panel so nothing is cut into the structure.

  1. Indoor view of a window infill panel with two round duct sleeves and a horizontal wall bracket, before the unit is hung
    1Prepare the openingsTwo duct sleeves through the infill panel and the wall bracket fixed above them.
  2. Outdoor view from the balcony: two vent covers on the window infill panel, with the unit visible inside
    2Finish the outsideTwo vent covers on the panel. No condenser, no line set on the façade.
  3. Finished room: the heat pump hung below the window between two armchairs
    3Hang the unit and connectThe unit hangs on the bracket, ducts aligned, and plugs in or is hard-wired.
  1. Mark the wall with the manufacturer's template and a spirit level, on a sound, flat exterior wall with room around the unit for airflow.
  2. Core two 8″ openings sloped 3–5° down to the outside, and fit the supplied duct sleeves, seam side up, trimmed flush inside.
  3. Route the condensate drain to a sanitary tie-in, floor drain, riser or the exterior wall, keeping a steady downward slope.
  4. Fit the vent covers from inside the room, or optional wall caps from outside where there's access.
  5. Hang the unit on the wall bracket, align the ducts and connect power: plug-in or hard-wired by model, to national wiring standards.

Minimum clearances and opening positions are on each model's wall mounting template in the spec sheet. Interior wall or old PTAC opening? See parts & accessories.

BUILT FOR ANY WEATHER

Rain or snow outside. The same comfort inside.

A real installation, inside and out. Everything that heats and cools sits indoors, sealed in the unit. Outside there are only two hooded wall caps facing down, so rain and snow run off instead of in.

Outside on a balcony: two black downward-facing hooded wall caps and a condensate drain on the window infill panel
OUTSIDETwo hooded caps. Nothing else.Downward-facing hoods shed rain and snow. No condenser, no line set, nothing on the balcony floor.
Inside the same suite: the heat pump installed below the window
INSIDEAll the equipment stays dry and warm.Compressor, coils and controls sit inside the room, away from the weather.
  • Water stays outHooded caps and duct sleeves sloped 3–5° down to the outside.
  • Nothing outdoors to ice upNo outdoor coil or fan on the balcony or roof.
  • Heats in the coldHeat pump heating rated down to 5°F (−15°C), with electric back-up heat.
REBATES & ELIGIBILITY

Applying for a rebate? Here's what programs ask for.

Incentive eligibility varies by province or state, utility and program, and most programs only accept equipment on their own qualifying list. Check eligibility with the rebate provider before you buy. We'll supply the model data and certificates your application needs.

  • Model number and equipment type, shown in the specifications table above.
  • AHRI certificate and reference number for AHRI-certified models (Standard 210/240).
  • Rated efficiency: SEER2, HSPF2 and EER2, plus heating capacity and COP at 5°F for cold-climate programs.
  • Safety listing: ETL (Intertek); the listing for each model is in the specifications table.
  • Installation by a licensed contractor, with the invoice showing model and serial numbers.

Sizing a project? Send us the rooms and we'll quote it.

Technical and warranty support: support@waysos.com · +1 604-401-0298